Drip trays that keep water off what matters

Drip trays and drain pans for data-centre pipework, AHUs, FCUs and VRF indoor units — made to the size of your unit or pipe run, in SS 304, hot-dip galvanised, GI, coated GI or aluminium, in lengths up to 5000 mm, at our plant in Pirangut, Pune.

  • 0.8–2.0 mm sheet
  • Lengths up to 5000 mm
  • 30–100 mm edge
  • Drain socket at the low point
  • Couplers for continuous runs
  • Datasheet and GA drawing for approval
Stainless steel drip tray with turned-up edges and a drain spigot (illustration)

Two kinds of drip tray

A drip tray is a shallow pan with a turned-up edge and a drain. It sits under anything that can sweat, drip or leak, and carries the water to a drain before it reaches a ceiling, a panel or a server rack.

Pipe-run trays

Long, narrow trays that run under chilled-water, condensate and liquid-cooling pipework — in data halls, hot and cold aisles, plant rooms and risers.

  • 100 to 750 mm wide
  • Lengths up to 5000 mm, or cut to your run
  • Joined with plate couplers into one continuous tray
  • Priced per running metre

Equipment pans

Pans made to the footprint of the unit above — AHUs, FCUs, VRF ductable, cassette and hi-wall units, and data-centre cooling equipment.

  • Made larger than the unit so nothing misses the pan
  • Sizes such as 750×750, 1200×750, 1460×1070 or 2800×800 mm
  • Insulated versions for chilled-water units
  • Priced per piece or per m², to match your BOQ

How a Pioneer drip tray is built

The tray hangs on threaded rods from cleats on each side, falls to a drain socket at its lowest point, and is made wider than the unit it protects.

Section drawing: drip tray on 8 mm rods under an indoor unit, 30 to 100 mm edge, base falling about 1 in 50 to a 15 mm drain socket, optional insulation underneath
Typical arrangement, drawn from approved shop drawings where Pioneer is the make. Your consultant's drawing always governs.

Specifications

The ranges below are what we have made and supplied for HVAC and data-centre projects. Anything outside them we make to drawing.

ItemPioneer drip trays
Materials
  • SS 304 — ASTM A240, mirror finish on one side
  • Hot-dip galvanised steel
  • Pre-galvanised GI — 120 / 180 / 275 GSM
  • Powder-coated GI, epoxy-coated GI and PPGI
  • Aluminium — aluminium grade to your specification; epoxy-coated aluminium
Sheet thickness0.8 mm (22 G), 1.0, 1.2, 1.5, 1.6 (16 SWG) and 2.0 mm
Edge (collar) height30, 50, 63 (2½ in), 75 and 100 mm
Pipe-run trays100, 150, 250, 300, 500, 600, 700 and 750 mm wide
LengthsUp to 5000 mm per tray; joined with couplers into continuous runs
Equipment pansMade to the unit size plus a margin, for example 750×750, 1200×750, 1400×750, 1460×1070, 970×550, 1460×820 and 2800×800 mm
Drain15 mm Ø drain socket typical; size, position and hose point to suit the site
Fall to drainAbout 1:50 on approved shop drawings
JointsPlate couplers 25 × 200 × 2 mm, 4 × M8 fasteners per coupler; SS 304 fasteners for stainless trays
HangingCleats for 8 mm threaded rods, or L-clips and 30 × 30 × 5 mm angles
Insulation (on request)13 mm nitrile rubber or 19 mm insulation under the pan
Raw materialJSW / TATA sheet
TolerancesLength ±10 mm, width ±3 mm, height ±2 mm
DocumentsDatasheet and GA drawing for approval; test certificates with the supply

Choosing the material

MaterialChoose it when
SS 304The tray must stay clean and rust-free for the life of the building — data halls, pharma, food, and anywhere a leak would be costly.
Hot-dip galvanisedThe specification asks for a heavy zinc coat and rules out electroplated GI. Hot-dip galvanising lays down a much thicker zinc layer than electro-galvanising.
Pre-galvanised GIHVAC units inside buildings. Specify the zinc: 120, 180 or 275 GSM. 275 GSM is the same coating US specifications call G90.
Powder-coated, epoxy-coated GI or PPGIYou want a painted barrier over the zinc, or a colour that matches the services.
Epoxy-coated aluminiumLarge pans where weight on the slab or the hangers matters.

Getting the size and slope right

A drain pan only works if water always has somewhere to go. ASHRAE Standard 62.1 asks that a drain pan:

  • slopes at least 10 mm per metre (⅛ inch per foot) toward the outlet, or otherwise drains freely with the fan on or off;
  • has its outlet at the lowest point, large enough not to overflow;
  • has a P-trap or other seal where the pan sits under negative pressure;
  • catches the full width of whatever drips, and stays reachable for cleaning.

The approved shop drawings our trays are made to use a fall of about 1 in 50 — 20 mm per metre, twice the ASHRAE minimum — and a tray roughly 150 to 300 mm larger than the unit overall. A 900 × 450 mm indoor unit, for example, gets a 1200 × 750 mm tray.

Under chilled-water units the pan itself gets cold and can sweat. That is why we offer trays with 13 mm nitrile or 19 mm insulation underneath.

Drip trays in data centres

Liquid cooling has brought water back into the white space. Data-centre specifications now call for drip trays under secondary-fluid and chilled-water pipework in the data hall, under pipe manifolds and flushing lines, and in both hot and cold aisles.

  • Tray sections joined into one continuous tray, so water flows to the drains without being stopped at a joint.
  • Hot-dip galvanised or SS 304 sheet, often with the edge turned up 63 mm (2½ in) or 100 mm (4 in).
  • Room in the tray for the leak-detection probes or sensing cable your BMS contractor fits.

We make the trays to the pipe routes on your layout, and the wire mesh and ladder trays for the same hall. See cable trays for data centres.

Specification clauses for your BOQ

For consultants: copy a clause into your BOQ or technical specification, then adjust sizes and quantities to your schedule. Words in [brackets] are alternatives.

Data centre pipework — SS 304 / HDG

Chilled-water and liquid-cooling pipework in data halls

1. Drip trays shall be provided under chilled-water and secondary-fluid pipework where shown on the drawings, fabricated from SS 304 sheet [hot-dip galvanised steel] 1.2 mm [1.5 mm] thick.
2. Trays shall have a turned-up edge of 63 mm [100 mm] and shall be joined with plate couplers into one continuous tray that drains to the outlets.
3. Tray lengths shall be up to 5000 mm, width as per the pipe routes on the drawings.
4. Each tray run shall fall about 1 in 50 to drain sockets at its low points; drain size and position as per the drawings.
5. Space shall be left in the tray for leak-detection cable or probes where specified.
6. Make: Pioneer Cable Trays or approved equivalent.

HVAC units — GI / aluminium pans

AHUs, FCUs, VRF ductable and cassette units

1. Drip trays shall be provided under each indoor unit where shown, fabricated from pre-galvanised steel sheet 275 GSM [SS 304 / aluminium] 0.8 mm [1.0 mm] thick.
2. Each tray shall be larger than the unit footprint by 150–300 mm overall, with an edge of 50 mm [75 mm].
3. The base shall fall about 1 in 50 [not less than 10 mm per metre, as per ASHRAE 62.1] to a 15 mm drain socket at the lowest point.
4. Trays under chilled-water units shall have 13 mm nitrile rubber insulation underneath [where specified].
5. Trays shall be hung on 8 mm threaded rods from cleats on each side.
6. Make: Pioneer Cable Trays or approved equivalent.

What to send for a quotation

  1. The unit list with sizes, or the pipe routes with lengths and widths.
  2. Material and finish, and the zinc coating (GSM) if GI.
  3. Sheet thickness and edge height.
  4. Drain size and position, and whether you need a hose point.
  5. How the tray will be hung, and whether it needs insulation.
  6. Quantities, site location and the date you need it on site.

We reply with a quotation, our datasheet and a GA drawing for approval.

Drip tray questions

Straight answers from our engineers. Ask us anything else on WhatsApp or by mail.

Which material should I choose for a drip tray?

SS 304 for data halls, pharma, food and anywhere the tray must stay clean and corrosion-free. Hot-dip galvanised steel where the specification excludes electroplated GI and asks for a heavy zinc coat. Pre-galvanised GI (120, 180 or 275 GSM), powder-coated, epoxy-coated GI or PPGI for HVAC units in buildings. Epoxy-coated aluminium where weight matters. Send us your BOQ line and we match it.

What edge height does a drip tray need?

Most HVAC unit pans use 50 or 75 mm. Data-centre pipework trays are often specified at 63 mm (2.5 in) or 100 mm (4 in). Shallow 30 mm trays are used under small drain pipes. We make 30, 50, 63, 75 and 100 mm as standard and other heights to drawing.

How much slope should a drain pan have?

ASHRAE Standard 62.1 asks for a drain pan that slopes at least 10 mm per metre (1/8 inch per foot) toward an outlet at its lowest point. Approved shop drawings where Pioneer is the make use a fall of about 1 in 50, which is 20 mm per metre.

How big should the drip tray be compared with the unit?

The tray must catch everything the unit drips, so it is made larger than the unit footprint. On approved shop drawings the tray is typically 150 to 300 mm larger overall, for example a 1200 x 750 mm tray under a 900 x 450 mm unit.

How are drip trays joined into a continuous run under pipework?

Tray lengths are joined with plate couplers (25 x 200 x 2 mm) and M8 fasteners so the run behaves as one continuous tray that drains to its outlets. Fasteners are SS 304 for stainless trays.

Do you supply insulated drip trays?

Yes. For chilled-water units we supply trays with 13 mm nitrile rubber or 19 mm insulation underneath, so the tray itself does not sweat.

Do you send a datasheet and drawing for approval?

Yes. Every drip tray order starts with our datasheet and a GA drawing for your consultant's approval, and test certificates go with the supply.

Do you price per piece, per metre or per square metre?

All three, to match your BOQ: per piece for equipment pans, per running metre for pipe-run trays, and per square metre where the BOQ measures that way.

Send your BOQ.We will price it.

Share your BOQ, drawings or specification. We reply with a quotation, ex-works Pune or FOB Nhava Sheva, with load data and test reports for your consultant.